中文版    English    
             
  NAME:Process Controller   MODEL:C4102     <<BACK
  Description   Specifications   Product Picture  
 

C4102 is a single Loop Process Controllers,which provide PID control of any analog process variable (temperature, pressure, level and flow) in batch and continuous process applications. It can be applied to all industrial fields including processing industry ,manufacturing industry ,mixed industry and so on .
Function:
①Multi-sensor input without hardware change.
②Control output: relay, linear 4-20mA, 0-20mA, Pulse output
③ 4 alarms.2 timer relay for alarms.
④Process Variable or analog transfer between setpoint 4-20mA and 0-20mA.
⑤Auto/Manual "bumpless" transfer.
⑥Programmable Soft Start (0 to 9999 seconds).
⑦RS485 communication; RTU MODBUS.
⑧Sensor Type:PT100;thermocouple J,K,T,N,S;0-5V;4-20mA;0-50mV
 


Dimension: 48x96x110mm (1/20 DIN).
Panel: 45.5x91 mm (+0.5 -0.0mm)
Power: 85-250VAC/DC, 50/60Hz. Max. Power Consumption: 3VA
Operating environment: 0-50 C
Humidity: 20-95% No condensing

Input:
1)   Keys input (refer to the Table1)
2)   Internal resolution: 19500
3)   Display resolution: 12000 ( -1999-9999)
4)   Sampling rate: five times each second
5)   Accuracy: thermocouple: 0.25%
Pt100 , 4-20mA, 0-50mV, 0-5Vdc: 0.2% 
6)   Input resistance: 0-50mV, Pt100 and thermocouple>2MΩ
0-5V: >1MΩ
4-20mA: 100
7)   Pt100 Measurement: DIN 43670 standard (б=0.00385). Current: 250uA.
8)   Analog Output: 0-20mA or 4-20mA, 1500 levels, Top Load 550 Ω.
Control Output (standard version, up to 4 outputs):
1) Two 3A / 250Vac (3A / 30Vdc) one normal open relay
2) One 3A/250VAC (3A / 30Vdc) one transfer relay
3) Isolated 0-20mA or 4-20mA control output or PV or SP transfer output, 1500 level resolution, Top load 550Ω;
4) SSR Logic Pulse: 0 or 20mA;
5) The above can be chosen as the main control output or alarm.
6) Programmable PWM cycle from 1 second to 100 seconds
7) 10 seconds after power-on, the control starts.
Optional unit (5 outputs)
1) Choice 1: 3A / 250Vac (3A / 30Vdc) SPDT relay ( the third relay)
2) Choice 2: RS-485, 1200 to 19200bps
ALARMS

  1. Up to 4 alarms, capable of setting 9 different functions

2) 2 relay alarms, programmable from 0 to 6500 seconds, 
3)  4 alarms have a programmable return difference;

 

 
 
View Original Image